JKBMS APP Settings Guide: LFP, NCM/NCA and LTO Batteries
Estimated reading time: 17 minutes
Condividi
This is a general JKBMS APP settings guide for LFP (LiFePO₄), NCM/NCA, and LTO (lithium titanate) batteries. It is not limited to the PB series. Available functions, labels, editable fields, and default values can vary with the connected BMS, firmware, and APP version. Always follow the actual device and its applicable documentation.
All screenshots illustrate the interface and how to operate its controls only. Their displayed numbers and switch positions are not recommended settings or a complete configuration to copy. The demonstration battery is identified as NCM/NCA. Its voltage parameters must not be copied into LFP or LTO batteries. All three are lithium-battery chemistries, but their operating voltages and requirements differ.
Part A: Simple Setup for Beginners
1. Select the Correct One-Click Preset
For beginners, especially those setting up LFP batteries, the recommended approach is the matching one-click preset rather than manually editing protection and control parameters. Confirm the actual chemistry from the battery or cell documentation first.
- Connect to the correct BMS and authorize settings using Verify Pwd.
- Select LFP for LiFePO₄, NCM/NCA for the corresponding supported cells, or LTO for lithium titanate. Confirm the preset operation as prompted.
- In Core Parameters, enter the actual Cell Count and Capacity (Ah).
- Apply the entries using their adjacent confirmation controls, then reopen the page and verify that they were received.
- Leave other parameters at the applicable preset or professionally commissioned configuration. If the equipment requires additional integration or the resulting settings are unsuitable for the cells, stop and obtain professional assistance rather than experimenting.
Beginner setup means selecting the correct preset and entering the battery’s core information, not manually tuning every page. The preset does not identify chemistry automatically, verify wiring, change the physical battery, or configure every external charger and inverter. Use compatible, correctly installed equipment within its ratings. A professional should handle any system-specific changes required before operation.
Applying another chemistry preset can overwrite working parameters. Do not press the shortcuts merely to inspect another chemistry after completing a custom configuration.
2. Core Parameters: Cell Count and Capacity
Cell Count: Enter the actual number of series-connected cell groups, such as 8 for 8S or 16 for 16S. Parallel connections do not increase the series count. Do not copy the demonstration’s eight-cell arrangement into a different battery.
Capacity (Ah): Enter the design capacity monitored by this BMS. A 16S1P battery using 320Ah cells is 320Ah. A 16S2P arrangement using 160Ah cells is nominally 320Ah when monitored as one bank. If parallel battery modules each have their own BMS, enter the capacity of the individual module, not the combined bank.
The Core Parameters section contains these basic battery entries. Other protection, balancing, heating, calibration, and communication pages are not additional beginner adjustments. Increasing the capacity entry does not increase physical capacity or current capability.
3. Why LFP, NCM/NCA, and LTO Need Different Presets
Each chemistry needs its own voltage-related settings. The following cell-level values are document-based reference settings for the configurations described, not measurements from the screenshots and not a guarantee of the exact values every firmware will load.
NCM/NCA reference: Overvoltage protection 4.20V; overvoltage recovery 4.17V; undervoltage protection 2.82V; undervoltage recovery 2.83V; automatic shutdown 2.80V.
LFP reference: Overvoltage protection 3.60V; overvoltage recovery 3.54V; undervoltage protection 2.60V; undervoltage recovery 2.65V; automatic shutdown 2.50V.
LTO reference: Overvoltage protection 2.70V; overvoltage recovery 2.64V; undervoltage protection 1.80V; undervoltage recovery 1.85V; automatic shutdown 1.75V.
These references explain why profiles cannot be exchanged. Beginners should use the matching one-click preset, not manually assemble a profile from these numbers. Protection thresholds are not automatic charging targets or daily discharge endpoints. Professionals must confirm applicability against the actual cell and BMS specifications.
Part B: Connection and Everyday Monitoring
4. Device List and Bluetooth Login

Device-name search: Identify the intended BMS. Device entry and signal bars: Select the correct device; signal strength is not battery health or SOC.
Search, Scan, and Group: Navigation entries whose workflows can vary with APP version. The supplied manual describes Bluetooth scanning and selecting a device. Do not assume Group automatically configures electrical parallel connections or communication addresses.

Login: Enter the Bluetooth connection password and press OK. The eye icon controls visibility. The manual lists 1234 as the default for its covered devices; use the actual password if changed.
Connecting... indicates an attempt, not confirmed receipt of battery data. Check device identity and connection before editing. Change default credentials and store them securely.
5. Device Name and Passwords

Pencil / Change the Rename: Device-name editing. The manual specifies English letters or numbers. The Bluetooth name is not the communication address.
Change the password: Changes the Bluetooth connection password using the existing password.

Verify Pwd.: Authorizes parameter editing. The manual lists 123456 as the default setting password for its covered devices. This is independent of the Bluetooth password.

Change password of settings: Enter the old password, replacement, and confirmation. Changing it does not automatically change the Bluetooth password. Do not publish screenshots containing passwords.
6. Home Screen

Chg / Dsg / PreDsg / Bal.: Indicated charging, discharging, pre-discharge, and balancing states. Central percentage: Displayed SOC, not a calibration target.
Voltage and current: Operating measurements. The manual uses positive current for charging and negative current for discharging. Zero current does not prove electrical isolation.
Click to view alarm: Inspect the alarm details rather than bypassing protection. High Cell / Low Cell: Highest and lowest measured cells. Volt.-Diff.: Their difference; 0.002V equals 2mV.
Bal.-Curr.: Actual balancing current, not the configured maximum. Balancing may be enabled while current is zero because conditions are unmet.
Capacity / Rem. Cap.: Capacity information, distinct from the design-capacity setting. The manual describes calculated actual capacity updating after a complete discharge-and-charge cycle; do not force deep cycling merely to change the display without applicable guidance.
High Temp.: Temperature summary; check individual sensors. Cell Type: Shows NCM/NCA in the example. Current / Power / Status: Momentary operating information, not proof that configuration is correct.
Part C: Advanced Settings for Qualified Professionals
The remaining configuration sections are for qualified professionals. Change them only according to actual cell specifications, battery condition, usage pattern, BMS capability, external equipment, and system requirements. Beginners should retain the applicable preset or commissioned settings and request assistance when a custom setup is needed.
All screenshot numbers and switch positions remain interface examples only. They are not recommendations for NCM/NCA, LFP, or LTO. APP-version differences can change functions and editability; the actual connected device takes precedence.
7. Quick Controls and Optional Functions
Import Param. / Export Param.: Save a backup where supported. Import only a configuration confirmed for the applicable hardware, firmware, chemistry, and installation.
Charge / Discharge: Control the corresponding switches; ON does not prove current is flowing or all protection conditions allow operation.
Emergency: Keep off during normal operation. The manual warns that it bypasses battery protection. It is not a way to clear unexplained alarms.
Dis-Limiter: Discharge current-limiting function. Configure only where supported and required by the actual system. Do not confuse this label with a separate control for disabling parallel charging current limiting. Available functions and behavior can vary with APP and device versions.
GPS Lock Chg / GPS Lock Dsg: Optional GPS-related charging/discharging restrictions. Enable only with the matching hardware and intended monitoring arrangement.
LCD Always On: Supported display-backlight control, not a battery protection threshold.
8. Active Balancer and Usage-Dependent Start Voltage

Balancer: Enables automatic balancing. The manual describes balancing requiring the switch on, the relevant cell voltage above its start threshold, and maximum cell difference above the trigger threshold.
Bal. Delta Volt.: Trigger difference. The manual gives capacity-based references of 0.005V above 50Ah and 0.010V below 50Ah. It does not specify the exact 50Ah boundary. Professionals should consider measurement stability and actual battery behavior; smaller is not automatically better.
Bal. Start Volt.: Defines the voltage region where balancing can operate. There is no single value appropriate to every battery or usage pattern. A 3.45V LFP reference is a suggested application setting, not a mandatory threshold.
New, verified well-matched cells: A professional may consider a lower balancing-start threshold within the chemistry-appropriate range, depending on the charging routine and actual cell behavior. Newness alone does not prove good matching.
Mixed-batch, aged, or less-consistent cells: A professional may consider a higher start threshold to focus balancing in the upper charging region. Base the choice on measured behavior rather than age alone. A higher threshold is not a repair for damaged cells or poor connections.
Usage matters: The selected threshold must be reachable under the intended charging routine. If charging ends at the same voltage as balancing start, the manual’s requirement to exceed that threshold means balancing is not guaranteed. Review actual cell voltages, voltage difference, and available balancing time together. Do not transfer an LFP threshold to LTO or NCM/NCA.
Max. Bal. Current: The manual recommends no more than 0.1C, additionally limited by the actual balancer and cell specifications. For example, 10Ah at 0.1C is 1A; 20Ah is 2A. A 2A balancer cannot exceed its hardware rating for a larger battery.
9. Voltage Protection and Charging Strategy
Cell OVP: Cell overvoltage protection. Cell OVPR: Recovery below that threshold. The manual describes charging protection when any cell exceeds its limit and recovery after all cells fall below recovery.
Cell RCV: Recommended charging voltage. It is separate from the protection threshold. Professionals can select a target according to chemistry, cell specification, and system requirements. For LFP storage applications, 3.45V and 3.50V per cell are separate reference choices, not a beginner instruction. For 16S, they correspond to 55.2V and 56.0V. Neither guarantees a particular SOC.
SOC-100% Volt. / SOC-0% Volt.: SOC recognition references, not extra protection limits or routine discharge endpoints. Keep them coordinated with the chosen charging strategy and the actual firmware. A lower charging target may not reach a higher full-charge recognition threshold. Do not select isolated SOC numbers from unrelated profiles.
Cell UVP: Cell undervoltage protection. Cell UVPR: Recovery above it. The manual describes discharge being disabled when any cell falls below its threshold, with recovery after all cells exceed recovery.
PwrOff Volt.: Automatic shutdown. The manual describes shutdown when even the highest cell voltage is below this value, which must be below undervoltage protection.
Compare chemistry-specific reference values in Part A, but verify actual applicability. Where a general manual’s SOC relationships and a model-specific preset differ, obtain clarification rather than assuming a universal rule.
Configure standalone chargers separately where they do not follow BMS requests. In normal operation, charger and load controls should operate within the battery’s permitted range rather than repeatedly relying on protection trips. Never widen thresholds to hide a weak cell or excessive load.
10. Current Protection and Precharge

Continued ChgCurr.: Charging-overcurrent threshold. Chg OCP Delay: Duration above it before protection. Chg OCPR Time: Recovery interval. These settings do not actively regulate every external charger.
Continued DsgCurr.: Discharge-overcurrent threshold. Dsg OCP Delay: Duration before protection. Dsg OCPR Time: Recovery interval. Select actual values within the cells, BMS, wiring, terminals, fuse, and equipment ratings.
Discharge OCP 2: An additional discharge-overcurrent protection function that can be selectively enabled where appropriate. Professionals should choose its use according to actual system requirements and supported behavior; do not infer its internal thresholds or timing from the switch alone.
PreDsg Time: Supported pre-discharge/precharge duration. The manual describes a resistor-based stage before discharge is enabled. A timer does not substitute for suitable hardware.
If a cell specification permits a selected charging rate of 0.5C, 100Ah corresponds to 50A, 200Ah to 100A, 280Ah to 140A, 314Ah to 157A, and 320Ah to 160A. These are calculations, not universal recommendations. A lower component rating governs. Beginners should not manually enter these examples instead of obtaining the correct preset or commissioned configuration.
11. Temperature Protection

Disable battery temp: Temperature-monitoring bypass control. Keep monitoring active in normal operation and repair sensor faults instead of masking alarms.
Charge OTP / OTPR: Charging high-temperature protection and recovery. Charge UTP / UTPR: Charging low-temperature protection and recovery.
Discharge OTP / OTPR: Discharge high-temperature protection and recovery. Discharge UTP / UTPR: Discharge low-temperature protection and recovery.
CMOS OTP / OTPR: MOS-related temperature protection and recovery. Editability and factory limits depend on the actual device. The screenshot differs from fixed values described for a design in the general manual; do not treat either as universal or try to override fixed hardware protections.
Professionals may configure supported temperature fields according to cell limits, operating current, sensor placement, thermal design, and system requirements. Charging and discharging can have different limits. High-temperature recovery should be below protection; low-temperature recovery should be above protection.
No screenshot temperature is a recommended limit. In particular, do not assume below-freezing charging is allowed for ordinary LFP cells, or assume every NCM/NCA or LTO cell has the same temperature capability. Follow the exact cell data and any current derating.
12. Short-Circuit Protection
SCP Delay (μs): Short-circuit delay in microseconds. SCPR Timer (s): Recovery interval in seconds. Do not confuse these units or copy the image numbers.
Keep the verified protection configuration unless qualified, model-specific instructions require a change. The manual warns that a setting of 0 disables short-circuit protection. Do not use that as a troubleshooting shortcut or deliberately short a battery to test it. A recovery timer does not prove the fault has cleared.
13. Heating Control

Dsg Heat: Discharge heating. Enable only where the actual system supports and requires it. Heater Test: Heating test function, to be used with the correct hardware and procedure by qualified personnel.
Heater Start Tmp. / Heater Stop Tmp.: Heating start and stop temperatures. Configure them according to the installed heating system, cell requirements, sensor arrangement, and firmware behavior; do not copy the image.
Without heating hardware, do not enable or test it. With supported hardware, keep heating control separate from permission to charge. Turning on a heater or reaching its stop point does not prove every cell is warm enough for charging. Retain temperature protection.
14. Alarms, Dry Contacts, and Emergency Duration
Intermittent alarm: Intermittent versus continuous alarm presentation for applicable outputs, not a change to battery protection thresholds.
LCD Buzzer Trigger: Event monitored for the buzzer. LCD Buzzer Trigger Val. / Release Val.: Its trigger and recovery values, with meaning and units determined by the event.
DRY1 Trigger / DRY2 Trigger: Selected event for each dry-contact function. Trigger Val. / Release Val.: Corresponding trigger and recovery thresholds. Check the event selection; zero threshold entries alone do not prove a function is disabled.
Alarm and protection temperatures are independently configured for the actual system where supported. The screenshots only show the fields and operation method; their alarm and shutdown numbers are not a coordinated recommendation. If a pre-protection warning is required, professionals should set and test the alarm so it occurs before the relevant protective action, with suitable margin.
Match dry-contact wiring and external circuitry to the actual contact ratings. A dry contact is not automatically a powered output or replacement for BMS power protection.
Emerg. Time (min): Emergency-mode duration in minutes. It does not make protection bypass safe; keep Emergency off in normal operation.
15. Smart Sleep, Logging, and User Fields

Smart Sleep: Enables supported sleep behavior. Smart Sleep Volt.: Voltage condition; the manual describes the highest cell being below it with no current for the configured interval. Use a chemistry-appropriate configuration.
Smart Sleep Time (h): Sleep-entry interval in the manual, not an automatic wake-up duration. Verify the actual device’s standby and wake requirements.
Device Address: Communication address, not cell count or Bluetooth name. Assignment and editability depend on hardware and firmware.
Timed Stored Data: Enables periodic logs. Data Store Period (s): Interval; 3600 seconds is one hour. An interval alone does not enable logging.
User Data 1 / 2: Integration-dependent fields. Preserve their values unless the use is understood; they are not charging limits or SOC targets.
16. CAN and UART Communication

CAN Protocol No.: Match the actual inverter or connected equipment, supported interface, wiring, and communication requirements.
UART1 Protocol No.: Protocol for the first listed UART. UART3 Protocol No.: Separate protocol selection. Match each to the actual physical port and equipment rather than copying screen selections.
UART2 Protocol No.: The demonstrated system uses default UART setting 21, which generally cannot be modified. Functions and editability may differ with APP or device versions. Follow the actual connected system; do not force a change simply because another version shows different behavior.
This is a general guide, not a universal port map. Communication and display compatibility are hardware-specific and are not established by selecting a chemistry preset. Use the wiring and protocol instructions for the actual model.
17. Charge Control
Charge Float Mode: Supported float behavior. RCV Time (h): Recommended-charge-voltage hold time, not total charging duration. Cell RFV (V): Recommended floating voltage per cell.
Professionals should coordinate these with the actual chemistry, cell requirements, charger/inverter, and firmware. The displayed NCM/NCA-related voltage is not a recommended value, including for other NCM/NCA installations. Configure standalone equipment separately where necessary. RFV timing and Re-Bulk options may vary with version.
18. Calibration and Maintenance
Volt. Calibration: Actual voltage-measurement calibration, not a charging target. Curr. Calibration: Actual current-measurement calibration, not the maximum permitted current. Use reliable reference measurements and the correct procedure.
SOC calibration / SOH calibration: Do not reset values merely to improve the display or conceal battery condition. These are not beginner setup steps.

CycleCapacity Cal. (Ah): Cycle-capacity adjustment, distinct from design and remaining capacity. Use only an approved procedure.
Time Calibration: Synchronizes with phone time as described in the manual. Erase History Data: Deletes history according to the actual function’s scope; preserve diagnostic records and verify before confirming.
Con. Wire Res.01–16 (mΩ): Connection-resistance settings described for multi-enclosure applications with supplier guidance. They are not the balance-wire self-test readings. Do not enter guessed compensation to hide poor wiring.
Part D: Understanding Status and Checking the Result
19. Real-Time Status

Bat. Power: Operating power. Capacity / Remain. Cap.: Capacity information, not independent proof of health. CMOS Temp.: MOS temperature, separate from battery sensors.
Battery T1 / T2 / T4 / T5: Sensor channels visible in this layout. NA is described as a sensor not installed; it is not measured zero or permission to ignore a required sensor.
Cell AVG: Mean cell voltage. Volt.-Diff.: Highest-to-lowest difference. Bal. Current: Active balancing current.
Cycle Count / Cycle Cap.: Cycle-related information; the manual relates cycle count to accumulated discharge and battery capacity. Zero does not prove a new battery.
Vtg C-: Internal diagnostic reading described as charger-input voltage minus battery voltage, not a charging target.
Heater Curr. / Heater: Heating reading and state. Emerg. Timer: Remaining emergency time in seconds, unlike the duration setting in minutes. Sleep Timer: Sleep-related timer; its precise counting behavior depends on the actual version.
Details Log: Record count, not fault severity. Curr. Limiter: Current-limiting function state, not hardware rating or the state of all protection.
Cell Type: Displayed chemistry. LCD Alarm / DRY1 Alarm / DRY2 Alarm: Output states; OFF does not prove the absence of every other alarm. Balancer: Read with voltage conditions and current.
Volt. / Current: Pack measurements. Cell Voltages: Individual measured channels; dashes are not voltage measurements. Verify against actual series count.
Balance Wire Resistance (Ω): Approximate self-test for connection problems, not precision cell internal resistance. Excessive values can prevent balancing. Do not confuse Ω here with adjustable mΩ connection-resistance entries or interpret an unused channel’s zero as proof of a perfect connection.
20. Top-Right Menu

System log / Detailed log: Diagnostic records; available detail and retention vary. History of Version: Available version information. Privacy and Protocol: APP information, not inverter protocol selection. Language Settings: Interface language, not chemistry.
Bluetooth Upgrade: Use only the correct model-specific upgrade procedure and files. Bind display screen: Requires compatible equipment and its actual binding instructions. About: Record available versions when requesting support.
21. Final Checks
- Confirm the correct battery chemistry and a BMS configuration compatible with the actual cells and equipment.
- For beginner configuration, apply the matching one-click preset and set only Core Parameters: Cell Count and Capacity. Obtain professional help for other required adjustments.
- For professional configuration, keep a backup and verify all interacting thresholds, operating limits, optional hardware, and external charger/inverter settings.
- Check wiring using the actual model’s diagram and qualified assistance where necessary. Avoid changing protection parameters during high-current operation.
- Apply each changed field using its confirmation control. These screens show OK; the manual refers to Set and describes an acknowledgment. Reopen the page and read the values back.
- Begin monitored low-current testing. Check individual cells, current, temperature sensors, balancing, and alarm details.
- Stop and investigate abnormal behavior. Do not bypass temperature monitoring, disable short-circuit protection, or use Emergency mode to force operation.
For beginners, keep it simple: select the correct one-click chemistry preset and enter the battery’s Core Parameters. Advanced settings are for qualified professionals working from the actual battery condition and system requirements, not from the numerical examples in a screenshot.
Further reading: JKBMS APP Settings Manual (PDF). For a separate model-specific installation example, see the PB V19 Wiring and APP Setup Guide; its hardware details must not be treated as universal.